From the chart below. select
the light fixtures (in watts) required to illuminate the
fountain unit. Then, select the length of cable needed form the command center
to
the lights. Allow for extra-cable length, because the cable will probably
run along the bottom of the lake or pond due to the weight of the cable. The
codes indicated in the chart refers to the cable gauge:
85802
#12/3
85804
#10/3 85806
#8/3
85808 #6/3
Please note that the cable has to be "one continuous run"
from the command center to the lights. Lights must be installed in multiples of
''
3
lights" Each circuit must contain
" 3 lights ".
Should the cable wire not be long enough, adding extra cable or additional connections
will cause the lights to operate incorrectly.
|
Lighting Cable
Chart |
Cable Lengths up to: |
|
Quantity &
Watts |
Circuits |
Volts |
Ground
Fault
Protection
|
Amps
Per
Circuit |
150 ft. |
200 ft. |
300 ft. |
450 ft. |
| 3
x 200 watts |
1 |
115 |
20
amp |
5.2 |
85802 |
85802 |
85804 |
85806 |
| 3
x 300 watts |
1 |
115 |
20
amp |
7.9 |
85804 |
85806 |
85808 |
n/a |
| 3
x 500 watts |
1 |
115 |
20
amp |
13.1 |
85804 |
85806 |
85808 |
n/a |
|
|